    Case Introduction
    • 1, the cabinet number is not standard, should be marked unit number. The unit number of the gas unit
    • 總體情況介紹:

      四川28

      1, the cabinet number is not standard, should be marked unit number. The unit number of the gas unit electronic management system is inconsistent with the actual number. (Completed, re-numbered)

      2, improve the test method of gas generator protection, such as gas generator high water temperature, high oil temperature protection, underfrequency protection, reverse power protection, and establish protection test records after improvement. (Unit protection is only indicated, and the test method has been notified to the manufacturer for redesign changes)

      3. At present, there are 10 sets of probes for gas leakage in the generator room, and 9 sets for practical application. No When the gas leakage reaches 1%, close the gas valve and all except the fan

      4, power supply and generator set chain shutdown protection. (Interlocking shutdown protection has notified the manufacturer to reset) The coupling protection cover of the gas generator set is too small, and the keyway is located outside the protective cover. (re-customized)

      5, improve all kinds of warning signs. (finished)

      6, improve the emergency plan, on-site equipped with anti-poison cover, protective clothing, etc. (The emergency plan has been completed, and the poison mask and protective clothing have been planned)

    上一條:山西20×500

    下一條:

    Jinan Jichai Huanneng Gas Power Generation Equipment Co., Ltd
    • 服務熱線

      0531-62325028
      0531-69951266

    Sichuan 28×500kW gas power generation project

    Do a project, build a monument

    1, the cabinet number is not standard, should be marked unit number. The unit number of the gas unit

    四川28

    1, the cabinet number is not standard, should be marked unit number. The unit number of the gas unit electronic management system is inconsistent with the actual number. (Completed, re-numbered)

    2, improve the test method of gas generator protection, such as gas generator high water temperature, high oil temperature protection, underfrequency protection, reverse power protection, and establish protection test records after improvement. (Unit protection is only indicated, and the test method has been notified to the manufacturer for redesign changes)

    3. At present, there are 10 sets of probes for gas leakage in the generator room, and 9 sets for practical application. No When the gas leakage reaches 1%, close the gas valve and all except the fan

    4, power supply and generator set chain shutdown protection. (Interlocking shutdown protection has notified the manufacturer to reset) The coupling protection cover of the gas generator set is too small, and the keyway is located outside the protective cover. (re-customized)

    5, improve all kinds of warning signs. (finished)

    6, improve the emergency plan, on-site equipped with anti-poison cover, protective clothing, etc. (The emergency plan has been completed, and the poison mask and protective clothing have been planned)